JL-HSVG Medium-Voltage Static Var Generator
JL-HSVG Medium-Voltage Static Var Generator

JL-HSVG Medium-Voltage Static Var Generator

The JL-HSVG series high-voltage static var generator is an IGBT-based dynamic reactive power compensation device. Connected in parallel to the power grid via a bridge converter circuit, it regulates output voltage or current to achieve dynamic reactive power compensation. Its core functions include improving power factor, suppressing harmonics, balancing three-phase grids, stabilizing voltage, and eliminating reactive power surges.

Product Overview

The JL-HSVG series high-voltage static var generator is an IGBT-based dynamic reactive power compensation device. Connected in parallel to the power grid via a bridge converter circuit, it regulates output voltage or current to achieve dynamic reactive power compensation. Its core functions include improving power factor, suppressing harmonics, balancing three-phase grids, stabilizing voltage, and eliminating reactive power surges. It is designed to address power quality issues in modern grids caused by renewable energy integration and non-linear loads. Featuring a modular design, the product offers advantages such as rapid dynamic response, strong harmonic suppression capabilities, and flexible operating modes, representing a state-of-the-art solution for reactive power compensation.

Performance Features

① Rapid dynamic response: Response time ≤ 5ms; tracks load changes in real-time.

② Strong harmonic suppression: Output current THD ≤ 3% at rated power.

③ Flexible operating modes: Supports six modes, including constant reactive power, constant power factor, and constant voltage; target valuesare adjustable in real-time.

④ Modular design: Power units are connected in a cascaded (series) configuration; easy maintenance and capacity expansion via parallel connection.

⑤ Comprehensive protection: Includes protection against overvoltage, undervoltage, overcurrent, and overheating; supports fault waveform recording.

⑥ High efficiency: Efficiency ≥ 99% under rated conditions; low heat generation and low operating costs.

⑦ Easy installation: Phase sequence independence allows for rapid grid connection; compact footprint.

Technical Parameters

Parameter CategorySpecific Specifications
Rated Operating Voltage6kV, 10kV, and other custom voltage ratings
Rated Capacity±1 to ±100 Mvar (continuously adjustable from inductive to capacitive)
Response Time≤5 ms
Overload Capability1.2 times rated capacity for 1 minute
Output Current THD≤3% at rated power
Output Voltage Distortion Rate≤5% prior to grid connection
System Efficiency≥99% under rated operating conditions
Operating Temperature-20°C to +40°C
Storage Temperature-30°C to +70°C
Altitude<2000 m (customization required for higher altitudes)
Protection RatingCompliant with GB/T 4208 standard (varies by model)

Operating Environment

① Environmental Conditions:

l Temperature: Operating temperature -20°C to +40°C, daily temperature variation ≤25K; storage temperature -30°C to +70°C.

l Humidity: Monthly average relative humidity ≤90% (at 25°C, non-condensing).

l Altitude: ≤2000m; special design required if this limit is exceeded.

l Environment: Free from conductive dust, corrosive gases, and explosive media; free from severe vibration.

② Installation Requirements:

l Clearance: ≥1500mm from the front to the wall; ≥1000mm from the rear/sides to the wall; ≥1500mm from the top to the ceiling.

l Ventilation: Good ventilation must be maintained; auxiliary cooling (e.g., air conditioning) is required if the temperature exceeds 38°C.

l Grounding: Cabinet grounding resistance ≤500mΩ; shielding layer reliably grounded.

③ Electrical Conditions:

l Grid Voltage Fluctuation: Within ±10% of rated voltage.

l Control Power Supply: AC220V/DC220V/AC380V; voltage deviation +7% to -10%.

Get a Free Quote

Feel free to contact us —
we strive to earn your trust.