The JL-HSVG series high-voltage static var generator is an IGBT-based dynamic reactive power compensation device. Connected in parallel to the power grid via a bridge converter circuit, it regulates output voltage or current to achieve dynamic reactive power compensation. Its core functions include improving power factor, suppressing harmonics, balancing three-phase grids, stabilizing voltage, and eliminating reactive power surges.
The JL-HSVG series high-voltage static var generator is an IGBT-based dynamic reactive power compensation device. Connected in parallel to the power grid via a bridge converter circuit, it regulates output voltage or current to achieve dynamic reactive power compensation. Its core functions include improving power factor, suppressing harmonics, balancing three-phase grids, stabilizing voltage, and eliminating reactive power surges. It is designed to address power quality issues in modern grids caused by renewable energy integration and non-linear loads. Featuring a modular design, the product offers advantages such as rapid dynamic response, strong harmonic suppression capabilities, and flexible operating modes, representing a state-of-the-art solution for reactive power compensation.
① Rapid dynamic response: Response time ≤ 5ms; tracks load changes in real-time.
② Strong harmonic suppression: Output current THD ≤ 3% at rated power.
③ Flexible operating modes: Supports six modes, including constant reactive power, constant power factor, and constant voltage; target valuesare adjustable in real-time.
④ Modular design: Power units are connected in a cascaded (series) configuration; easy maintenance and capacity expansion via parallel connection.
⑤ Comprehensive protection: Includes protection against overvoltage, undervoltage, overcurrent, and overheating; supports fault waveform recording.
⑥ High efficiency: Efficiency ≥ 99% under rated conditions; low heat generation and low operating costs.
⑦ Easy installation: Phase sequence independence allows for rapid grid connection; compact footprint.
| Parameter Category | Specific Specifications |
| Rated Operating Voltage | 6kV, 10kV, and other custom voltage ratings |
| Rated Capacity | ±1 to ±100 Mvar (continuously adjustable from inductive to capacitive) |
| Response Time | ≤5 ms |
| Overload Capability | 1.2 times rated capacity for 1 minute |
| Output Current THD | ≤3% at rated power |
| Output Voltage Distortion Rate | ≤5% prior to grid connection |
| System Efficiency | ≥99% under rated operating conditions |
| Operating Temperature | -20°C to +40°C |
| Storage Temperature | -30°C to +70°C |
| Altitude | <2000 m (customization required for higher altitudes) |
| Protection Rating | Compliant with GB/T 4208 standard (varies by model) |
① Environmental Conditions:
l Temperature: Operating temperature -20°C to +40°C, daily temperature variation ≤25K; storage temperature -30°C to +70°C.
l Humidity: Monthly average relative humidity ≤90% (at 25°C, non-condensing).
l Altitude: ≤2000m; special design required if this limit is exceeded.
l Environment: Free from conductive dust, corrosive gases, and explosive media; free from severe vibration.
② Installation Requirements:
l Clearance: ≥1500mm from the front to the wall; ≥1000mm from the rear/sides to the wall; ≥1500mm from the top to the ceiling.
l Ventilation: Good ventilation must be maintained; auxiliary cooling (e.g., air conditioning) is required if the temperature exceeds 38°C.
l Grounding: Cabinet grounding resistance ≤500mΩ; shielding layer reliably grounded.
③ Electrical Conditions:
l Grid Voltage Fluctuation: Within ±10% of rated voltage.
l Control Power Supply: AC220V/DC220V/AC380V; voltage deviation +7% to -10%.