The JL-3000 series reactive power compensation controller is primarily designed for the automatic control and protection of 1–2 main transformers and 1–3 capacitor banks. Its core algorithm comprehensively evaluates voltage fluctuations and reactive power deficits; by intelligently switching capacitor banks, it balances reactive power supply and demand, improves supply voltage quality, and reduces energy loss, ultimately achieving higher power factors and lower system losses.
The JL-3000 series reactive power compensation controller is primarily designed for the automatic control and protection of 1–2 main transformers and 1–3 capacitor banks. Its core algorithm comprehensively evaluates voltage fluctuations and reactive power deficits; by intelligently switching capacitor banks, it balances reactive power supply and demand, improves supply voltage quality, and reduces energy loss, ultimately achieving higher power factors and lower system losses.
(1)Grouping and Regulation: Supports equal/unequal capacity grouping; utilizes a switching method for 1–3 capacitor banks.
(2)Harmonic Handling: Features harmonic display and protection functions; harmonic analysis is performed when secondary voltage ≥ 50V and secondary current ≥ 0.5A.
(3)Auxiliary Functions: Optional cloud service capability (availability depends on the specific model).
(4)Power Supply Compatibility: Supports AC 220V ±15% or DC 220V ±15% power input.
(5)Human-Machine Interface: Equipped with a 4.3-inch LCD screen (480×272) and supports button-based operation.
(6)Communication Capabilities: Uses an RS485 interface and supports communication protocols such as Modbus, CDT, IEC101, and IEC103.
| Item | Details |
| External dimensions | 321×181×110mm(Length × Width × Thickness) |
| Panel cutout dimensions | 306×178mm(Length × Width) |
| Operating power | Rated voltage: AC/DC 220V (-20% to +10%),ripple factor ≤5%;Power consumption: ≤10W (normal), ≤15W (during operation). |
| Supply Rated sampling parameters | Busbar voltage: AC 100V (≤0.5VA per channel) Open‑delta voltage: AC 57.7V (≤0.5VA per channel) Current: 5A (≤0.5VA per channel) |
(1)Operating environment: Temperature -10°C to +55°C, relative humidity 5% to 95% (non-condensing).
(2)Storage and transportation: Temperature -25°C to +70°C, relative humidity ≤85%.